Chapter III. Equipment of air ventilation systems

As indicated above, the required state of the air environment in the premises is maintained by general exchange ventilation methods by pumping clean ventilation air into the premises with the necessary temperature-humidity parameters and removal of air that does not meet regulatory requirements. In accordance with this, general exchange ventilation systems should include equipment and devices for intake of outdoor air, its processing, transportation and distribution around the premises, as well as for the removal of exhaust air.

3.1. Air intake and air discharge devices

These include air intake and air discharge devices in mechanical ventilation systems, which are made in the form of holes in the fences of buildings, attached or freestanding shafts. When air is taken from above, the air intake devices are placed in the attic or upper floor of the building, and the channels are removed above the roof in the form of shafts.

For aeration, air intake and ejection devices are made in the form of rotating transoms, opening lanterns, windows or other overlapping apertures in the fences of buildings.

The location and design of the air intake devices are selected taking into account the cleanliness of the intake air and the satisfaction of architectural requirements. Thus, air intake devices should not be located near sources of air pollution (emissions of polluted air or gases, chimneys, kitchens, unpaved roads, etc.).

Air intake apertures should be located at a height of at least 2 m from the ground surface and closed with louvered grilles (in the green zone – at a height of at least 1 m).

To protect the premises from outside cold air during standby of the ventilation through ventilation ducts, air intake and air discharge devices are equipped with multi-leaf insulated valves with manual or mechanical drive. In the latter case, the valve is blocked along with the fan closing the apertures. At low temperature of the outside air, the valves are supplied with an electric heating system in order to protect their flaps from freezing. Electric heating is turned on for 10–15 minutes before starting the fan (Fig.2).


Fig.2. Electric air valve


The outer walls of exhaust ducts and shafts are insulated to avoid condensation and ice of water vapor from the extracted moist air. The air velocity in the supply channels and shafts is supported between 2 and 5 m/s, in the channels and shafts of exhaust devices: 4–8 m/s, but not less than 0.5 m/s, including for natural ventilation.

3.2. Ventilation chambers

The main ventilation equipment of supply and exhaust installations, as a rule, is installed in special rooms called ventilation chambers. Supply chambers in public, administrative, residential buildings are usually designed on the ground floor or in the technical underground. Exhaust chambers should be located in the upper part of the building. In multi-storey buildings with a large number of ventilation systems, ventilation chambers are arranged in technical floors.

In buildings with a large number of ventilation systems (more than 5), a room for equipment repair is provided. The operation of ventilation systems is controlled from special remote controls using automation and remote control devices.

3.3. Fans

The fan is a mechanical device designed to move air through the ducts of ventilation systems, as well as to carry out direct air supply to the room or suction from the room, and creating the pressure drop necessary for this (at the inlet and outlet fan). According to the design and principle of operation, fans are divided into:), radial (centrifugal), diametral (tangential) (Fig.3).


Fig.3.Fan designs


Currently, modifications of radial fans are used – direct-flow, disk, vortex, tornado (Fig.4).


Fig.4. Modifications of radial fans


Fans are evaluated by specific speed, which relates the rotational speed and pressure.

We divide fans into three groups, depending on the magnitude of the total air pressure they create: low pressure (up to 1 kPa), the maximum circumferential speed of such wheels does not exceed 50 m/s; medium pressure (up to 3 kPa), the maximum circumferential speed reaches 80 m/s; high pressure (up to 12 kPa), the circumferential speed of the impellers is more than 80 m/s.

The separation of fans by pressure is conditional, since any high-pressure fan with a decrease in the speed of rotation can be used as a medium-pressure fan.

In the direction of rotation of the impeller (when viewed from the suction side), the fans can be of right rotation (the wheel rotates clockwise) and left rotation (the wheel rotates counterclockwise).

Depending on the composition of the transported medium and operating conditions, fans are divided into: conventional – for air (gases) with a temperature of up to 80 °C, corrosion-resistant – for corrosive environments, heat-resistant – for air with a temperature above 80 °C, explosion-proof – for explosive environments, dust-proof – for dusty air (solid impurities in the amount of more than 100 mg/m3). According to the method of connecting the fan impeller and the electric motor, the fans can be: with a direct connection, with a connection on an elastic coupling, with a V-belt transmission, with an adjustable stepless transmission.

At the place of installation, fans are divided into: conventional, mounted on a special support (frame, foundation, etc.), ducted, installed directly in the duct, roof, placed on the roof.

The main characteristics of the fans are the following parameters: air consumption (m3/h), total pressure (Pa), rotation speed – rotations per minute (rpm), power consumption spent on the fan drive (kW), EFFICIENCY – the efficiency of the fan, taking into account mechanical power losses due to various types of friction in the fan working bodies, volume losses as a result of leaks through seals and aerodynamic losses in the flow part of the fan, the sound pressure level (dB).

3.4. Supply installations

The supply units (Fig.5) filter fresh air, if necessary, heat it (in the cold season) and supply it to the duct system for subsequent distribution around the premises.


Fig.5. The supply unit


Inlet ventilation units consist of a housing in which are mounted: filter, water or electric heater, fan, automation system, sound insulation material,

Conditionally, Inlet installations can be divided into several types:

by type of heater (with an electric heater or with a water heater), by air consumption (up to 200–3000 m3/h – mini-supply installations, more than 3000 m3/h – central supply installations), by design (for vertical installation, for horizontal mounting, universal)

The automatic control system of the supply unit allows you to gradually or smoothly adjust the thermal power of the electric heater. If a water heater is used in the supply unit, then the automation has a more complex design, since in this case it is necessary to provide additional protection against freezing of the heater in winter.

In ventilation systems with supply installations, the following additional elements can be used: air intake grilles, a valve for supply air (with an electric drive or manual drive), mufflers, devices for adjusting air flow in rooms, air distribution devices (diffusers, grilles, plafonds).

Structurally, the chambers are a monoblock structure and can be equipped with automatic control of various levels of complexity from simple functions such as START, STOP, OPEN-CLOSE VALVE, to programmable control of parameters (room temperature, performance, temperature inside the chamber, etc.) along a continuous circuit.

The supply chamber includes the following elements:

A double-sided suction fan, which is attached to the frame traverses through rubber vibration isolators. The frame is made of aluminum profiles and connecting corners.

Insulated panels made of galvanized steel on the outside and inside. Foam insulation is laid in the panel as a heater and sound insulator. For tightness, a self-adhesive sealer is laid between the panels and the frame. On one side of the camera, for ease of maintenance, the panels are made quick-detachable, for which they are equipped with rotary clamps.

Heater (water heater or electric heating elements).

Soft insert made of rubberized fabric with flanges on both sides. The flanges are made of a galvanized tire connected by corners.

Quick-release air filter.

Insulated air valve with electric drive.

To create a balance of the incoming and outgoing air from the room, exhaust ventilation is used, which can be represented by:

• autonomous axial fans installed directly in the wall;

• roof fans installed on the roof;

• centrifugal fans mounted on brackets in the wall or on metal roof structures;

• duct fans in a shell-shaped housing or in a box-shaped housing installed in a network of air ducts (have a nozzle at the inlet and a diffuser at the outlet, and in the case of installing a two-way suction fan – two at the inlet and one at the outlet).

• exhaust ventilation units equipped with fans, flexible inserts, control valves and assembled in a single housing (Fig. 6).


Fig.6 Exhaust system


Supply and exhaust ventilation systems can significantly reduce heating costs by using heat recovery. The heat removed from the room air can be used to heat the supply air in special heat exchangers called recuperators.

Such a system, using a cross-flow recuperator and made in the form of a monoblock, is characterized by a high efficiency of heat recovery, reaching 70%, and provides at least a twofold reduction in operating costs for air heating due to heat recovery (Fig.7).


Fig.7. Supply and exhaust system with recovery


Heat recovery units are designed for the organization of supply and exhaust ventilation in comfortable air conditioning systems, i.e. they change the temperature and humidity of incoming fresh air taking into account the climatic conditions inside the serviced room.

The cross-flow plate regenerative heat exchanger is made of a heat-conducting material having the property of selective permeability with respect to water molecules (practically the membrane is impermeable with respect to molecules of other gases and substances). Due to this, the difference in the partial pressures of water vapor in the outdoor and exhaust air leads to the transfer of moisture from one stream to another. In the cold season, water molecules from the wetter exhaust air penetrate through the membrane into the outside air stream, humidifying it. In the warm season, water molecules from the wetter outdoor air penetrate into the exhaust air stream, preventing excessive humidification of the room.

3.5. Heaters

To heat the air in the supply ventilation units, heaters (air heaters) are used.


Fig.8. Water heater


High-temperature water or steam is used as a heat carrier for heaters. When the heating liquid is water, the heaters are marked as HW, when steam is marked as HS.

Heaters designed to work with a steam coolant are manufactured single – pass, with a water coolant-both single-pass and multi-pass. In single-pass heaters, the coolant passes through the entire bundle of tubes simultaneously from one collector to another, and in multi-pass collectors are separated by internal partitions that repeatedly change the direction of movement of the coolant, which increases the speed of water movement through the tubes and, as a consequence, increases the heat transfer of the heater. The connection of fittings in single-pass heaters is diagonal, and in multi-pass ones it is one-sided (Fig. 9).


Fig. 9. The flow diagram of the coolant in the heaters:

a – single–pass; b – multi-pass



Fins in the form of plates (plate heaters) or wound steel tape (spiral-wound heaters) are placed on the tubes to increase the contact area with the air passing through the heater. The outer fins are galvanized to reduce corrosion and better contact of the fins with the tubes. Fittings for the coolant are welded into the collectors, and to protect the fins from damage from the side, side shields are welded between the collectors. Flanges are used to connect the heater to adjacent elements of the ventilation system.

The arrangement of the tubes with the heating liquid can be consistent in the direction of air movement (corridor), staggered and offset along the corridor (most effectively). The tubes themselves can be either round or flat-oval in cross-section.

The best thermal engineering indicators have spiral-rolled bimetallic three- and four-row heaters for both steam (single-pass) and water (multi-pass) heater. The tubes for the heat carrier in these heaters are steel, the fins are rolled from aluminum.

Heaters are often grouped into several pieces, both with a parallel installation through the air, and with a sequential or combined one. If the heat carrier is steam, then the heaters are installed with a vertical arrangement of tubes and steam supply to the upper branch pipe; if the heat carrier is water, then the position of the tubes should be horizontal, which ensures the removal of air when filling the heaters with water and draining water from it when the system stops working.

Electric heaters are also available (Fig.10).


Fig.10. Electric heater


Electric heaters consist of a steel casing with tubular heating elements: 1.6 or 2.5 kW each. To increase the heating surface area, the heating elements have ribs with a diameter of 42 mm. Electric heaters can work both in manual and automatic mode, maintaining a constant temperature of the air at the outlet or in the room.

3.6. Duct heaters

The duct heater is used to heat the supply (outdoor) air in the ducts (conventional circular section). In central ventilation systems, duct heaters are used as auxiliary heaters, and in decentralized ones – as the main air heaters.

The heater body is made of galvanized steel. Air heating is carried out by heating elements. It is mandatory to have protective and regulating thermostats, which provides the product with high safety and the ability to function in automatic mode at the same time.

Channel heaters are equipped with two thermostats for overheating protection: heat-protective with automatic restart (operating temperature +50 °C) and fire-fighting with manual restart (operating temperature +110 °C). Channel heaters are designed for a minimum air flow velocity of 1.5 m/s and a maximum operating temperature of 40 °C of the outgoing air.

3.7. Air coolers

Duct air coolers (Fig. 11) are designed for cooling and dehumidification of supply, recirculating air or a mixture thereof in ventilation and air conditioning systems of industrial, public or residential buildings.


Fig. 11. Air cooler with ducted water and freon coolers


Water or non-freezing mixtures can be used as a refrigerant in ducted water coolers. The maximum allowable liquid pressure in them is 1.6 Mpa.

Freons are used as a refrigerant in ducted freon coolers. Upon delivery, the heat exchangers are filled with inert gas, which must be removed during connection to the refrigeration circuit.

The design of the cooler is a housing made of galvanized steel, inside which a heat exchanger, a drop trap and a pallet are installed.

The heat exchanger is made of copper tubes with aluminum fins arranged in a staggered order.

The freon cooler is distinguished by the design of the distribution unit ("spider") and the specifics of the refrigerant supply.

The collectors of the freon heat exchanger are made of copper tubes.

The drip trap (Fig. 12) is a set of special plastic plates that effectively trap condensate and collect it into a tray located in the lower part of the cooler body.


Fig. 12. The shape of the droplet trap plates.


The pallet is additionally thermally insulated and equipped with a discharge pipe for draining condensate

When installing the air cooler, it is necessary to ensure its horizontal position.

3.8. Filters

Filters are divided into three classes according to their effectiveness. Class I filters trap dust particles of all sizes (the cleaning coefficient is not less than 0.99), Class II filters – particles of more than 1 micron (cleaning coefficient is more than 0.85), class III filters – particles of more than 10–50 microns (cleaning coefficient is not less than 0.60).

3.9. Noise suppression equipment

The noise level generated by ventilation systems is an essential criterion of ventilation quality. The sources of noise in ventilation installations are fans and electric motors, as well as the movement of air in the ducts and its exit from the holes. Two types of noise are considered: aerodynamic and mechanical.

The reasons for the appearance of aerodynamic noise in fans are: the formation of vortices and their periodic disruption from the blades of the impeller, local air flows at the entrance to the wheel and at the exit from it, leading to unsteady flow around the blades of the wheel, perturbation of the medium by rotating blades. Mechanical noise occurs in bearings, in the drive, in the installation sites (fasteners) of the ventilation unit on building structures, etc. The degree of noise increases with insufficient balancing of the fan impeller.

Of all the sources of noise generation, the dominant ones are fans that create aerodynamic noise. The noise generated by the ventilation system can be reduced by the following measures: installation of fans with the most advanced acoustic characteristics, in particular, fans with blades bent backwards; the choice of fans with the highest efficiency (not less than 0.9 of the maximum), with a minimum angular velocity of the impeller (not higher than 30 m/s), i.e. fans with a small diameter of the impeller and a small number of revolutions (at the same time, you should not overestimate the pressure against the calculated one, since this causes an increase in noise level); careful balancing of the impeller.

Noise reduction along the path of its propagation is achieved by limiting the speed of air movement in the ducts or lining the inner surfaces of the ducts with a sound-proofing material.

In order to reduce the transmission of fan vibration to the ducts, the latter must be connected to the fan nozzles using soft inserts made of rubber, rubberized tarpaulin.

Vibration noise reduction is achieved by installing ventilation units on vibration isolators. Standard designs of spring and rubber vibration isolators are used (Fig. 13).


Fig. 13. Vibration Isolator


With the number of revolutions of the impeller up to 1800 rpm, it is recommended to use spring vibration isolators, characterized by stability of elastic properties, allowing large deflection and weakening vibrations even at very low frequencies. With large numbers of revolutions, the use of rubber vibration isolators is allowed.

In order to reduce the transmission of vibration to the structure of the building, fans should be mounted on their own concrete foundations on the ground. In the case of installation of ventilation units on the load-bearing structures of buildings, the plates or beams on which they are located must be mounted on vibration-absorbing supports.

The reduction of the noise level transmitted from the ventilation chamber to adjacent rooms is achieved by the installation of fences around it from structures with increased sound absorption, as well as the use of sound-absorbing linings in chambers and rooms. In ventilation chambers, it is possible to arrange "floating" floors consisting of layers of fiberglass plates, soundproof strips, etc.

. For active muffling of aerodynamic noise, mufflers are widely used in ventilation systems, the principle of operation of which is based on the conversion of sound energy into thermal energy by friction.

By their design, silencers are divided into tubular, honeycomb, plate and chamber silencers (Fig. 14).


Fig. 14. Muffler designs

a – lamellar with extreme plates; b – lamellar without extreme plates; c – tubular rectangular section; d – tubular circular section; e – chamber;

1 – muffler casing; 2 – sound – absorbing plate; 3 – air channels; 4 – sound-absorbing lining; 5 – internal partition;

A – the distance between the plates; B – the thickness of the plates; H, Hx – the dimensions of the duct; C -the thickness of the lining of the duct; D – the diameter of the duct


By design, silencers are divided into tubular, cellular, plate and chamber.

Tubular silencers are made round, rectangular. Cellular and plate silencers are made only rectangular. As a sound-absorbing material, soft mats made of superfine fiberglass with a thickness of 100 mm are used for tubular and cellular silencers and with a thickness of 100, 200 and 400 mm for plate silencers. To prevent the entrainment of the fiber with the air flow, the sound-absorbing layer is protected with fiberglass and metal mesh or perforated sheets with a perforation of at least 20%.

The plate silencer is a box made of a thin metal sheet. A tubular silencer is made in the form of two round or rectangular pipes inserted into one another. Tubular silencers are used on air ducts with a diameter of up to 500 mm.

Currently, active silencers have been developed that carry out broadband active noise suppression (especially effective at low frequencies). Noise neutralization is carried out by introducing antiphase noise.

3.10. Check valves

Check valves are used to allow air to pass in one direction and prevent it from moving in the opposite direction. They are available in two of the simplest modifications: the "butterfly" type and the "inertial lattice" type (Fig. 15).


Fig. 15. Check valves


The butterfly valve is made of galvanized steel, has two spring-loaded lobes, and can be installed in any position.

A petal check valve of the "inertial grid" type with light plastic blinds inserted into a galvanized steel box can only be installed on horizontal air ducts, under the action of the air flow in the permitted direction, the petals rise, in all other cases they are lowered.

One of the main characteristics of check valves is the maximum possible air velocity.

Check valves are used to prevent air flow: when several supply units are operating on the same network; when installing a backup supply or exhaust fan; when connecting several exhaust systems to one exhaust shaft.

They are also installed to prevent backflow of air when exhaust air is released onto the facade or in front of roof fans.

3.11. Air curtains

Air curtains (without air heating) they are arranged between rooms with the same or similar thermal conditions. They are used to prevent access of air from some rooms in which harmful vapors or gases are released to others.

The principle of operation of air-heat curtains is as follows: air is taken from the upper area of the lobby, heated in heaters up to 50 °C, fed by a fan into the air distribution chamber and then released through the uniform distribution duct at the door. The air is discharged through cracks or holes in the duct. The resulting jet creates a vertical air curtain. The air can be released from the bottom at the door or from the side to the desired height. Air is supplied to the air curtain from the supply ventilation without additional heating.

According to the principle and effect of the curtain, there can be gate and mixing types. In the first case, the curtain maximally or completely prevents (blocks) air access to the enclosed space; the air velocity from the installation to create such curtains should be high (up to 25 m/s). Such curtains are arranged at low outdoor temperature and frequent opening of doors. In mixing type installations, the rushing cold air is mixed with the heated air of the heat curtain. As a result, warm air enters the room through the door and the curtain, which does not create a feeling of cold blowing.

Questions to Chapter 3

1. What is the reason for the location of outdoor air intake devices in ventilation systems?

2. Name the main types of fans by type and design.

3. What is the reason for the mandatory installation of the filter in front of the heat exchange equipment (heaters and coolers)?

4. Give an example in which cases it is advantageous to use electric air heaters.

5. What are the advantages of using water heaters?

6. Why the range of air velocity in heat exchange equipment is strictly limited?

7. What is the fundamental difference between water (water-glycol) and freon air coolers?

8. What measures are envisaged to reduce noise in ventilation systems?

9. Which device is used to prevent air flow when the fan is turned off?

10. In which places of the building are provided air heat curtains with heated air?